How to choose
How to choose
When selecting a control panel cooler, determine the cooling capacity required to maintain the desired temperature inside the control panel. The required cooling capacity varies depending on factors such as the amount of heat generated inside the panel, the ambient temperature, the desired temperature inside the panel, and the installation location.
1. How to select panel cooler [indoor installation]
cooling capacity required to maintain the desired temperature inside panel can be calculated using the formula below.
Required cooling capacity [W]
= ①Total heat generation in panel [W] + ②Heat transfer rate [W/m2・℃] × (③Maximum ambient temperature [℃]-④ Desired temperature inside the board [℃]) × ⑤Control panel effective surface area [m2]
If you know the values for the total heat generated inside the control panel, the heat transfer rate, and other such figures,Model Selection GuideThis makes it easy to calculate the required cooling capacity.
①Total heat generation inside panel
The total heat generated by the devices housed inside the panel.
*For the heat output of each device, please refer to the heat output list by device.
② Heat transfer rate
The rate at which heat penetrates from outside the panel into the panel.
This varies depending on the type of sheet metal and thickness, but for a 2mm thick steel plate it is approximately 5 [W/m2・℃].
③ Maximum ambient temperature
The highest temperature expected in the installation environment.
Check the highest temperature expected in the environment where the control panel will be installed, such as during the height of summer.
④ Desired temperature inside the panel
Desired board temperature (the recommended temperature is 35°C).
If you set the desired temperature inside the cabinet too low, it not only makes condensation more likely to occur, but also extends the cooling time and increases power consumption.
⑤ panel effective surface area
The total surface area of all surfaces of the target control panel that come into contact with the atmosphere. For freestanding panels, this refers to the surface area excluding the bottom surface.
For wall-mounted installations, the calculation excludes surfaces that do not come into contact with the atmosphere, such as the back panel.
2. How to select panel cooler [outdoor installation]
For outdoor installation, add the amount of energy from sunlight to the selection result of panel cooler for indoor installation calculated in 1. panel cooler selection method [indoor installation].
Required Cooling Capacity [W]
=Total Solar Heat Gain+ Required cooling capacity when used as an indoor unit (1. How to Select a Control Panel Cooler [Indoor Installation](See ...)
How to calculate total solar radiation and heat penetration
1) Calculate the amount of heat entering through solar radiation.
The amount of sunlight varies depending on the installation location, date, time and orientation.
*Sample data of solar radiation on each surface (Tokyo area, July 22nd, clear skies) Unit: W/m²
| Top | north face | East side | south side | West side | |
|---|---|---|---|---|---|
| 11 o'clock | 1026.7 | 302.8 | 302.8 | 305.1 | 77.3 |
| 12 o'clock | 1064.0 | 78.3 | 78.3 | 325.9 | 78.3 |
| 13:00 | 1043.0 | 78.8 | 78.8 | 310.1 | 307.7 |
| 14:00 | 980.2 | 79.1 | 79.1 | 261.7 | 523.3 |
| 3pm | 872.1 | 80.7 | 80.7 | 179.8 | 715.3 |
Therefore, the required amount of solar heat radiation is calculated for each surface and the sum of the calculations is the amount of solar heat radiation required. The solar heat radiation for each surface can be calculated using the following formula.
Solar radiation on each surface [W/m²] ×
Terminology
- Heat transfer coefficient (W/m² °C): Ratio of the amount of heat that enters (or dissipates) by heat conduction to the area when there is a temperature difference between the ambient temperature (the temperature at which the enclosure surface rises) and the desired temperature. panel varies depending on the board thickness and material, but is defined as 5 to 6 W/m² °C by the Panel Heat Related Equipment Manufacturers Association.
- "Heat transfer coefficient on the outside of the housing (W/m²・℃)" - It is estimated to be approximately 10W/m²・℃ when there is no wind, and approximately 15W/m²・℃ when the wind speed is 1 to 2 m/s. The higher the wind speed, the greater the heat transfer coefficient.
- "Casing surface temperature rise (equivalent to outside air temperature rise)": This refers to the equivalent temperature rise due to solar radiation.
From the above, we can see that the temperature will vary depending on the area where the panel is installed, the color and condition of the panel surface, the condition of the panel's outer walls (thickness, double structure, installation of sunshades, etc.), and the condition of the wind circulating outside the panel.
As an example, let's calculate using panel with the following conditions.
◎ Height 2000mm, width 1000mm, depth 500mm◎ Door facing south◎ Tokyo area, July 22nd, clear skies, 2pm, no wind◎ Panel thickness 2mm, paint color: light beige, wall surface is single-layer structure
| Face position | solar radiation (W/m²) |
solar absorptance | Outer surface of the housing heat transfer coefficient (W/m²・℃) |
Fairly open air Temperature rise (℃) |
heat transfer rate (W/m²・℃) |
Area of surface (m²) | Solar heat (W) |
|---|---|---|---|---|---|---|---|
| Top | 980.2 | 0.5 | 10 | 49.01 | 5 | 0.5 | 122.5 |
| north face | 79.1 | 0.5 | 10 | 3.955 | 5 | 2 | 39.6 |
| East side | 79.1 | 0.5 | 10 | 3.955 | 5 | 1 | 19.8 |
| south side | 261.7 | 0.5 | 10 | 13.085 | 5 | 2 | 130.9 |
| West side | 523.3 | 0.5 | 10 | 26.165 | 5 | 1 | 130.8 |
| Total solar radiation and heat infiltration | 443.6 | ||||||
Caution! As the surface of the disc becomes dull over time, the absorption rate changes, so it is necessary to select a product with safety factor in mind.
2) Select the appropriate unit by matching the required cooling capacity listed above to the capacity-performance curve for each control panel cooler.
<<Notes on selection>>
- Please note that the amount of heat generated by inverters, servo amplifiers, etc. varies greatly depending on how they are used, motor torque, etc.
- For inverters with a rating output of 50 kW or more, the amount of heat generated varies greatly depending on the manufacturer, so please check with the manufacturer.
- When selecting a model, please select one that exceeds the required rating capacity and cooling capacity.
- Please note that capacity calculated using the above formula are only a guideline and are not absolute values.
- Please note that depending on the sealing of the panel, the position with the heating element, and the convection in the chamber, the expected cooling capacity may not be obtained.
- Dirty filter and deterioration of the fan motor may lead to a decrease in cooling capacity, so please perform regular maintenance.
List of heat output by device
1. power supply and transformer equipment
| Equipment stored inside the panel | Heat generation (reference value) | Remarks | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| transformer | rating capacity
|
|
||||||||||||||||||
| Voltage regulator | rating capacity
|
|
||||||||||||||||||
| AC power supply supply stabilized power supply |
rating output capacity
|
|
||||||||||||||||||
| Uninterruptible power supply (UPS) |
Approximately 10-15% of rating output capacity. |
|
||||||||||||||||||
| DC stabilized power supply (switching regulator) |
rating output capacity
|
|
||||||||||||||||||
| Low-Voltage Capacitor | Approximately 0.15 to 0.2% of rating capacity |
|
||||||||||||||||||
| lead acid battery | Q(W) = I × V × n |
|
2. Amplifiers
| Equipment stored inside the panel | Heat generation (reference value) | Remarks | |||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AC servo amplifier | rating Output
|
|
|||||||||||||||||||||||||||||||||
| Inverter | rating Output
|
|
|||||||||||||||||||||||||||||||||
| Large inverter (200V system) |
rating Output
|
||||||||||||||||||||||||||||||||||
| Large inverter (400V system) |
rating Output
|
|
|||||||||||||||||||||||||||||||||
| Thyristor | rating current
|
|
|||||||||||||||||||||||||||||||||
| Power conditioner | rating output (kW) × (1 - Power conversion efficiency % / 100) |
|
3. Wiring equipment
| Equipment stored inside the panel | Heat generation (reference value) | Remarks | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Circuit breaker (MCCB) |
rating current
|
|
||||||||||||||||
| Earth leakage circuit breaker (ELCB) | rating current
|
|
||||||||||||||||
| Electromagnetic contactor | rating capacity
|
|
||||||||||||||||
| Thermal overload relay (thermal) |
rating current
|
|
||||||||||||||||
| Electromagnetic relay | 4W程度 |
|
4. Control equipment
| Equipment stored inside the panel | Heat generation (reference value) | Remarks | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Small relay |
|
power consumption of the coil is considered as the amount of heat generated. | |||||||||||||||
| Solid State Relay (SSR) |
|
Output ON voltage drop: approximately 1.6 to 1.8V. | |||||||||||||||
| Temperature controller | power consumption is considered equivalent to heat generation. | ||||||||||||||||
| PLC | Integrated PLC (All-in-One Type): power consumption is considered as heat generation. Reference (items with limited expansion/expansion capabilities) - AC power supply
Other PLCs (Base, power supply, CPU unit configuration): power consumption of power supply unit is considered as power consumption |
|
5. Information and communication equipment
| Equipment stored inside the panel | Heat generation (reference value) | Remarks |
|---|---|---|
| PC main unit | power consumption is considered equivalent to heat generation. | |
| monitor | ||
| server | ||
| Switching hub | ||
| router | ||
| Media converter | ||
| booster | power consumption- Transmission power | |
| display | LED display: power consumption x approximately 0.7 LCD: power consumption is considered as heat generation. |
6. Others
| Equipment stored inside the panel | Heat generation (reference value) | Remarks | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Fan motor |
|
|
remarks
(1) When calculating from rating capacity (VA) and rating output (VA), the heat generation amount (W) is obtained by multiplying by the percentage (%).
(2) Actual heat generation varies depending on the equipment, so it is necessary to check the catalogs and technical documents of each manufacturer.
(3) Wiring and other small components can also be sources of heat, so this must be taken into consideration.
Product information for Apiste 's Enclosure Cooling Unit can be found here.