Enclosure cooling unit (Freon/Special specification)

  1. HOME
  2. Enclosure Cooling Unit ENC Series
  3. Model list
  4. ENC-G2240L
Enclosure Cooling Unit Enclosure Cooling Unit (refrigerant/special specification) ENC-G2240L

Enclosure Cooling Unit (refrigerant/special specification)
ENC-G2240L

Cooling capacity(W)*1 2000/2200
Rated voltage(V) Three-phase 380 to 415V AC/400 to 460V AC
Mounting Type Side-mounting
External Dimensions(mm) H1200×W450×D260
Weight(kg) 62

ENC-G2240L Product details

(50/60Hz)

Mounting Type Side-mounting
Cooling capacity(W)*1 2000/2200
Setting temperature range (℃) 25~45
Ambient temperature(℃) 20~55
Ambient humidity(%RH) 10~85 (No condensation)
External Dimensions(mm) H1200×W450×D260
Weight(kg) 62
Coating Color Munsell 5Y7/1 light beige equivalent
Rated voltage(V) Three-phase 380 to 415V AC/400 to 460V AC
current consumption: rating (A) * 1.7/1.9
Current consumption *3 : Max(A) *5 2.2/2.5
Starting current (A) December 13
power consumption: rating (W) * 1000/1200
Power consumption *3 : Max(W) *5 1350/1700
Noise resistance Fast transient/burst immunity test level 4
Vibration resistance Equivalent to JIS Z 0200 Level1
Dust and water proof protection rating Equivalent to IP54 (internal circulation route)
Certification
refrigerant types R134a
refrigerant filling amount (g) 300
Noise (dB(A)) 約65/67
External output alarm output (non-voltage contact: 250V 2A resistive load)
Display Internal temperature/error display LED RUN LED

Note)
cooling capacity: rating capacity value when outside temperature is 35°C and internal temperature setting is 35°C - 40%. (Measurement conditions: JIS-C-9612 air enthalpy method)
Use Area Temperature and humidity conditions for use area Humidity are not guaranteed to be met.
rating: Value when Use Area Temperature 35°C and use area Humidity 40% RH.
MAX value: The value when Use Area Temperature is the maximum allowable ambient temperature and use area Humidity is 40% RH.
- Use power-supply voltage within ±10% of rated voltage.
- Be sure to read the instruction manual carefully before use and use it correctly.

External dimensions

ENC-G2240L Dimensions

Diagram of Panel Cutout

ENC-G2240L installation diagram

Capacity characteristics graph

ENC-G2240L capacity characteristics graph

*Contact our sales representative if you are using the control panel cooler in an environment close to the permissible ambient temperature upper limit.

【Note】
Please read the instruction manual before use and use the product correctly.
◯Products will be delivered to the vehicle (at designated locations within Japan, excluding remote islands).
Depending on model and number of units, a separate charter service (additional fees apply) may be required.
◯For overseas deliveries, we recommend using separate overseas packaging.
Please check specification of Enclosure Cooling Unit and install an appropriate circuit breaker (wiring breaker) between Enclosure Cooling Unit and power supply.
Using the device outside of rating power supply range may cause malfunctions.
Please perform regular maintenance.
Neglecting regular maintenance can lead to product performance degradation and malfunctions.
◯During winter when outside temperatures are low, do not operate Enclosure Cooling Unit continuously.
When disposal of this product, please do so in accordance with all applicable laws and regulations.

If you are having trouble selecting a product or would like to discuss implementation,
please feel free to contact us.

Inquiry

For product inquiries, quote requests, etc.
Please feel free to contact us.

TEL: 0120-945-354

This service is not available from some IP phones.

support@apiste.co.jp